加载中

3500kW 400Vac 电阻、无功、容性负载箱,用于发电机测试

2026-01-08

客户为提升发电机组运行稳定性需开展发电机测试,因此采购了我司集成式阻感负载箱。

项目概述

客户为提升发电机组运行稳定性需开展发电机测试,因此采购了我司集成式阻感负载箱。

项目要素

说明
项目地点Malaysia
环境Altitude of 2500 meters
产品规格3500kW RLC Load Bank 690Vac 50Hz
数量2 units
应用场景Generator testing
备注The client needs to conduct generator testing for improved operating stability, therefore they purchased our integrated resistive-inductive load bank.

负载箱技术规格

设备型号:3750 kW   400Vac Resistive&Reactive&Capacitive Load Bank For Generator testing.
主要电气参数
负载类型Resistive&Inductive&Capacitive
测试功率AC400V,3 phase
频率50Hz/60Hz
容量3500kW,2551KVAR,1332.8KVAR
功率因数Lead 0.95 PF, Lag 0.8 PF
负载精度±3%
三相平衡Unbalance: ≤3%
绝缘等级F
设计■ Outdoor: Reference Pictures-Outdoor Design
时间定额Continuous design/temporary
步进(1KW +2KW*2 + 5KW + 10KW*2 + 20KW + 50KW+65KW +115KW*2+230KW*6)*2
电抗器Min.step: 1kvar; A Line@400V-50HZ-1100kVAR,Steps: 1kvar  2kvar*2  5kvar  10kvar*2  20kvar 50kvar 204kvar*6; B Line@400V-50HZ-1100kVAR,Steps: 204kvar*6;
冷却系统Cooling mode:Forced air cooling,horizontal air inlet/outlet
运输4 Lifting holes at the top four corners of the load bank.
尺寸(L*W*H) 9800mm*2438mm*2900mm
重量23T
主要部件Contactor: ABB/Schneider brand Circuit breaker: ABB/Schneider brand PLC: Siemens Fuse: Delixi
温度-20℃ to 50℃
湿度up to 100%
海拔up to 2500m
大气压力86 to 106kPa

产品照片

图片1 拷贝 (4) 图片2 拷贝 (3) 3 拷贝 (7) 4 拷贝 (5) 5 拷贝 (5) 6 拷贝

产品亮点

  • 任一风机风量不足时自动卸载并报警
  • 风机电源开关未开启前无法加载负载
  • 3500kW大功率RLC测试
  • 多维安全保护
  • 智能状态指示
  • 模块化设计便于维护
上一篇:3750kVA 功率因数 0.8 690V 交流阻感式负载箱,用于发电机测试下一篇:40 台施耐德 100kW 电阻交流负载箱产品案例研究
为您推荐
联系我们
您可以通过以下方式联系我们,或填写留言表单,我们将尽快回复您。
联系方式
欢迎随时与我们联系,无论是产品咨询还是技术支持,我们都会第一时间响应。
联系人
李经理
电话
19382122423
微信
chengcui1128
地址
四川省德阳市罗江区金山工业园红玉路东段
留言
客户服务
detect