加载中

瑞泰 7500kVA 发电机负载测试配大功率电阻及无功负载箱

2026-01-05

瑞泰承制的7500kVA负载箱应用于广东阳江核电站现场测试项目,圆满通过10小时不间断满功率带载试验。

项目概述

瑞泰承制的7500kVA负载箱应用于广东阳江核电站现场测试项目,圆满通过10小时不间断满功率带载试验。

负载箱技术规格

设备型号:RATA 8250kVA Resistive & Reactive Load Bank
主要电气参数
系统组成Load enclosure, high‑voltage switchgear, dry‑type transformer, resistive load, inductive load, acquisition system, control system, cooling system and protection system
有功功率6000kW
无功功率4500kVAR
视在功率7500kVA
额定负载电压AC380V (stepped‑down to 380V via transformer)
额定频率50Hz
负载特性Integrated resistive‑inductive load; resistors and reactors can be switched on and off independently
功率因数PF=0.8~1.0 adjustable
负载连接Three‑phase four‑wires Three‑phase Balance Unbalance degree ≤ ±2%
加载精度≤ ±2%
加载步进值10kW / 7.5kVAR
冷却方式Forced air cooling with fan‑centric modular design
风机电源Dual‑power supply (internal / external) with automatic fast transfer
进出风方式Side air intake, top air outlet
负载温升Temperature rise ≤120℃ at 1‑meter position from air outlet
运行方式Continuous‑duty operation
负载控制电源AC380V/50Hz
测量显示精度±0.5%FS
绝缘等级Class F
电阻材料Special‑alloy resistors Load Control‑Control Mode Local / Remote System Parameters‑Control Mode Manual / Automatic
加载功能Independent loading & combined loading (supports parallel‑operation with on‑site AC6.6kV‑4200kW‑RL and AC6.6kV‑3000kVA‑RL/AC mobile test loads)
测量控制功能A, V, Hz, kW, cosΦ acquisition and display
控制响应时间≤200ms
负载保护Short‑circuit, over‑temperature, abnormal airflow, emergency stop and other protections
运行环境温度‑20℃ ~ +50℃
运行环境湿度50% ~ 95%
运行海拔2000 m and below
相对湿度≤95%, non‑condensing Atmospheric Pressure 86‑106 kPa
箱体尺寸13000 mm × 2438 mm × 2896 mm (L × W × H)
重量Approx. 20 tons per unit
防护等级IP54
应用场所Outdoor (salt‑spray, dust, rain‑snow resistant)
安装与运输Load‑bearing lifting lugs fitted at four corners of enclosure to satisfy hoisting requirements
负载扩展Parallel expansion of 1+N load containers
箱体颜色Subject to customer requirements
应用范围Suitable for gas‑turbine generator sets, marine diesel generator sets, land‑based diesel generator sets and UPS systems
应用场景After the completion of manufacturing of the load equipment, the following tests shall be carried out: rated power and load‑capacity test, load‑regulation accuracy test, electrical‑parameter fluctuation test under various working conditions, temperature‑rise test, overload and protection‑function test, insulation test, power‑frequency withstand‑voltage test, enclosure protection‑rating test, earthing test, and continuous full‑load capability test (full‑load operation for no less than 24 hours).

客户需求

高可靠性并联运行:作为主设备,本机可与现场现有AC6.6kV-4200kW-RL移动测试负载和AC6.6kV-3000kVA-RL/AC移动测试负载并联运行、互为热备用,确保故障设备可在不停机应急柴油发电机的情况下与系统电气隔离。

系统采用以风机为核心的负载联动智能容错与保护设计:单台风机故障仅切断其关联负载,不影响其他模块运行;冷却风机具备双电源自动快速切换功能;电阻/电抗单元设有温度监测与过热保护,过热时仅切除故障负载,风机保持运行并记录详细事件日志。

全方位安全措施:电气系统各功率级均配置短路保护,变压器进线端设有过流及瞬动过流保护;设备防护等级IP54,可雨中运行;所有电缆采用无卤阻燃材质并具备充分隔热保护。

灵活控制与数据记录:支持远程/本地控制模式切换,切换过程负载状态保持不变;控制系统可完整记录操作日志与测试参数分析,存储容量100M,支持二次曲线绘图。

严格验证标准:设备交付前将进行不少于10小时的不间断满功率实际负载测试,验证长时间运行稳定性。

应用场景

负载设备制造完成后将进行以下测试:额定功率与负载能力测试、负载调节精度测试、各工况下电气参数波动测试、温升测试、过载与保护功能测试、绝缘测试、工频耐压测试、箱体防护等级测试、接地测试及连续满负荷能力测试(满负荷运行不少于24小时)。

产品照片

33da8f77febe2626451f52dc8a1a3517_副本 ec725abec54fad479560f4e21e07cc79_副本 1a73b08379d8846e7b09eb954ab5dac2_副本 3_副本 0 (9) IMG_5666_副本 IMG_5697_副本 4204eda2c241e51f9cfd628286676d37_副本

产品亮点

  • 7500kVA大容量阻感负载
  • 有功与无功负载独立调节
  • 面向6.6kV应急发电机测试设计
  • 以风机为核心的模块化故障隔离
  • 冷却风机双电源自动快速切换
  • 强制风冷与温度保护
  • 智能测量、控制与测试数据记录
  • 多套负载系统并联运行
  • 适应沿海盐雾环境防护
上一篇:阿联酋数据中心应用 960 台 18kW 机架式负载箱项目下一篇:瑞泰 SIRLC-4000L 船舶发电机负载测试配大功率电阻、无功及容性负载箱
为您推荐
联系我们
您可以通过以下方式联系我们,或填写留言表单,我们将尽快回复您。
联系方式
欢迎随时与我们联系,无论是产品咨询还是技术支持,我们都会第一时间响应。
联系人
李经理
电话
19382122423
微信
chengcui1128
地址
四川省德阳市罗江区金山工业园红玉路东段
留言
客户服务
detect